Description / Abstract:
This SAE Aerospace Recommended Practice (ARP) contains
guidelines and recommendations for subsonic airplane air
conditioning systems and components, including requirements, design
philosophy, testing and ambient conditions.
The airplane air conditioning system comprises that arrangement
of equipment, controls and indicators that supply and distribute
air to the occupied compartments for ventilation, pressurization,
and temperature and moisture control. The principal features of the
system are:
a. A supply of outside air with independent control
valve(s).
b. A means for heating
c. A means for cooling (air or vapor cycle units and heat
exchangers)
d. A means for removing excess moisture from the air supply
e. A ventilation subsystem
f. A temperature control subsystem
g. A pressure control subsystem
Other system components for treating cabin air such as
filtration and humidification are included, as are the ancillary
functions of equipment cooling and cargo compartment
conditioning.
The interface with the major associated system, the pneumatic
system (Chapter 36 of ATA 100) is at the inlet of the air
conditioning shutoff valves. This boundary definition aligns with
that in the ATA 100 Specification.
Purpose
The purpose of this ARP is to provide guidance for the design,
installation, and analysis of subsonic airplane air conditioning
systems.
Field of Application
This ARP applies to subsonic airplane air conditioning systems
within the ATA 100 Specification, Chapter 21. ATA Chapter 21 covers
the air conditioning system that maintains passenger and crew
environment, and ATA 21 also encompasses cabin pressure control
systems. This ARP does contain cabin pressurization control
guidelines; however the focus is on air conditioning systems. Refer
to ARP1270 for detailed recommendations on cabin pressure control
systems.